FCB 22000
Electronic direct starter panel
Electronic direct starter panel for 2 motors for pressure boosters, clean water and wastewater, with display.
• Multi-application panel
• Motor data self-learning
• Alarm and event data logger
• Motor maintenance data logger
• Remote control
• Single-phase version with power relay for inductive loads (up to 31A)
• Motherboard protection
• Operating voltage 230Vac +15/-20% 50/60Hz (SA694.xx)
• Operating voltage 400Vac +15/-20% 50/60Hz (SA697.xx)
• Main isolator switch with door lock
• Button for automatic operation
• Button for manual operation (stable/unstable)
• Siren mute button
• Auxiliary circuit protection fuse
• Motor protection fuse
• No. 2 contactors (SA697.xx)
• External enclosure in thermoplastic material
• Cable glands
• IP65 protection rating
• Operating temperature -5/+50°C
• Relative humidity 60% at 50°C (non-condensing)
INPUTS/OUTPUTS
• No. 4 extra-low voltage inputs
• 4-20mA input
• No. 2 extra-low voltage inputs for motor Klixon
• No. 2 12Vdc alarm outputs, max. 200mA, for siren and LED flashing light
• Alarm output max. 5A NC-COM-NO (dry contact)
PROTECTIONS
• Minimum and maximum current protection for each motor with alarm
• Phase failure and phase sequence protection with automatic reset and alarm
• Minimum and maximum voltage protection with automatic reset and alarm
• Klixon protection for each motor with automatic reset and alarm
ADVANTAGES
• Multilingual LCD display for viewing:
– Mains voltage
– Current for each motor
– Hour counter for each motor
– Pressure switch status
– Level status
– System pressure with pressure transducer
– Tank level in metres with piezoresistive probe
– All messages relating to motor operation
• Self-learning of maximum and minimum current for each motor
• Adjustable maximum number of starts per hour
• Adjustable motor start test (24-48-72-96h)
• Dry running with level control and minimum current
• Adjustable probe sensitivity
• Deactivatable alternation of the 2 motors
• 3s delay between the starting of the 2 motors
• Automatic switching in the event of motor failure
• Pressure loss control
• Adjustable mains return delay
• Siren mute
• Operation with pressure switches, floats, probes, pressure transducer and 4-20mA piezoresistive probe